Software Start-Up and Ref. Owner manual
Table Of Contents
- GV3000/SE AC General Purpose (V/Hz) and Vector Duty Drive, 1 - 20 HP, 230V AC Software Start-Up and Reference Manual D2-3387-5
- Important User Information
- Document Update
- Summary of Changes
- Table of Contents
- List of Figures
- List of Tables
- Preface
- Chapter 1 - Starting Up the Drive for Volts/Hertz Regulation
- Chapter 2 - Starting Up the Drive for Vector Regulation
- Chapter 3 - Using the Keypad/Display To Program, Monitor, and Control the Drive
- Chapter 4 - Programming Reference
- Chapter 5 - Troubleshooting the Drive Using Error Codes
- Appendix A - Alphabetical Listing of Parameters
- Appendix B - Record of User Parameter Settings
- Appendix C - Power Module-Dependent Parameter Default Values (230 V Series)
- Appendix D - Default Parameter Settings
- Appendix E - Configuring the Digital Inputs When the RMI Board Is Installed in the Drive
- Appendix F - Using the Terminal Strip Analog Input
- Appendix G - Drive Regulation Overview
- Back Cover / Publication D2-3387-5 July 2013

4-46
GV3000/SE 230 VAC Drive, Software Reference Version 6.04
P.055 STOP/RESET Key Disable
This parameter
disables the
STOP/RESET key
except from the
selected control
source.
ATTENTION: When P.055 is set to ON, the STOP/RESET key is
functional only from the selected control source. As a safety
precaution, Reliance Electric recommends that an emergency stop
push button be located near the drive in an easily accessible location.
As a further safety precaution, the user should post a warning on the
drive to alert personnel that the STOP/RESET key is not functional.
Failure to observe this precaution could result in severe bodily injury or
loss of life.
Table 4.7 details whether the STOP/RESET key is active based on the selected
control source (P.000) and P.055.
Table 4.7 – STOP/1n P.000 and P.055
!
Control Source
(P.000 =)
Front panel (LOCL)
Terminal strip (rE)
Network/option board (OP)
OIM/CS3000 (SErL)
Front panel (LOCL)
Terminal strip (rE)
Network/option board (OP)
OIM/CS3000 (SErL)
P.055
OFF
OFF
OFF
OFF
ON
ON
ON
ON
Front Panel
STOP/RESET Key
Active
Active
Active
Active
Active
Inactive
Inactive
Inactive
OIM/CS3000
STOP/RESET Key
Active
Active
Active
Active
Inactive
Inactive
Inactive
Active
Parameter Range: OFF = Enable the STOP/RESET key regardless of
the control source
ON = Disable the STOP/RESET key except from the
selected control source
Default Setting: OFF
Parameter Type: Tunable
Refer also to parameters: P.000 Control Source