Software Start-Up and Ref. Owner manual
Table Of Contents
- GV3000/SE AC General Purpose (V/Hz) and Vector Duty Drive, 1 - 20 HP, 230V AC Software Start-Up and Reference Manual D2-3387-5
- Important User Information
- Document Update
- Summary of Changes
- Table of Contents
- List of Figures
- List of Tables
- Preface
- Chapter 1 - Starting Up the Drive for Volts/Hertz Regulation
- Chapter 2 - Starting Up the Drive for Vector Regulation
- Chapter 3 - Using the Keypad/Display To Program, Monitor, and Control the Drive
- Chapter 4 - Programming Reference
- Chapter 5 - Troubleshooting the Drive Using Error Codes
- Appendix A - Alphabetical Listing of Parameters
- Appendix B - Record of User Parameter Settings
- Appendix C - Power Module-Dependent Parameter Default Values (230 V Series)
- Appendix D - Default Parameter Settings
- Appendix E - Configuring the Digital Inputs When the RMI Board Is Installed in the Drive
- Appendix F - Using the Terminal Strip Analog Input
- Appendix G - Drive Regulation Overview
- Back Cover / Publication D2-3387-5 July 2013

4-40
GV3000/SE 230 VAC Drive, Software Reference Version 6.04
P.050 Restore Defaults
This parameter
resets all First and
Second Menu
General parameters
(P.---) to factory
default settings.
Parameter Range: OFF = No action
ON = Reset parameters to default settings
Default Setting: OFF
Parameter Type: Configurable
Refer also to parameters: P.049 Country Defaults
Note that P.048 (Volts/Hertz or Vector Regulation) is not restored to its factory
default setting when P.050 is set to ON.
P.051 Programming Disable
When the password
is entered into this
parameter,
parameter values
cannot be modified
from the keypad
unless the correct
password is entered
again. Refer to
section 4.4, Ensuring
Program Security, for
more information.
Parameter Range: 0 to 9999
Default Setting: 0 (Programming enabled)
Parameter Type: Tunable
Refer also to parameters: N/A
ATTENTION: It is user's responsibility to determine how to distribute
the password. Reliance Electric is not responsible for unauthorized
access violations within the user's organization. Failure to observe this
precaution could result in bodily injury.
The PASSWORD LED will be on to indicate parameters cannot be modified from
the keypad.
Note that disabling program changes by means of P.051 will not prevent parameter
changes being made from the serial port on the network.
!