Software Start-Up and Ref. Owner manual
Table Of Contents
- GV3000/SE AC General Purpose (V/Hz) and Vector Duty Drive, 1 - 20 HP, 230V AC Software Start-Up and Reference Manual D2-3387-5
- Important User Information
- Document Update
- Summary of Changes
- Table of Contents
- List of Figures
- List of Tables
- Preface
- Chapter 1 - Starting Up the Drive for Volts/Hertz Regulation
- Chapter 2 - Starting Up the Drive for Vector Regulation
- Chapter 3 - Using the Keypad/Display To Program, Monitor, and Control the Drive
- Chapter 4 - Programming Reference
- Chapter 5 - Troubleshooting the Drive Using Error Codes
- Appendix A - Alphabetical Listing of Parameters
- Appendix B - Record of User Parameter Settings
- Appendix C - Power Module-Dependent Parameter Default Values (230 V Series)
- Appendix D - Default Parameter Settings
- Appendix E - Configuring the Digital Inputs When the RMI Board Is Installed in the Drive
- Appendix F - Using the Terminal Strip Analog Input
- Appendix G - Drive Regulation Overview
- Back Cover / Publication D2-3387-5 July 2013

4-32
GV3000/SE 230 VAC Drive, Software Reference Version 6.04
P.029 Elapsed Time Meter
This parameter
displays the number
of days (24-hour
periods) that the
drive has been under
power or the time
elapsed since the
Elapsed Time Meter
Reset (P.030)
parameter was last
reset.
Parameter Range: 0 to 9999 days
Default Setting: N/A
Parameter Type: Read only
Refer also to parameters: P.030 Elapsed Time Meter Reset
P.030 Elapsed Time Meter Reset
Parameter Range: OFF = No action
ON = Reset the Elapsed Time Meter (P.029) and
the error log clock to zero (0).
Default Setting: OFF
Parameter Type: Tunable
Refer also to parameters: P.029 Elapsed Time Meter
P.031 to P.038 Preset Speed 1 Through Preset Speed 8
This parameter
allows the setting of
up to eight different
preset speeds.
The presets are configured using parameters P.007 and P.008. P.008 must be set
to values of 2 through 7 for preset speeds. See table 4.4 and figure 4.6.
Parameter Range: Minimum Speed (P.003) to Maximum Speed (P.004)
Default Setting: 5.0 Hz (V/Hz)
150 RPM (vector)
Parameter Type: Tunable
Refer also to parameters: P.007 Terminal Strip Digital Inputs Configure
P.008 Terminal Strip Speed Reference Source
This parameter sets
parameter P.029
(Elapsed Time
Meter) and the error
log clock to zero.
This parameter is set
to OFF after the
reset operation is
carried out.