User Manual

WebPak 3000 Drives: Register Map
7-9
9 Current memory
10 Memory save
11 Current/speed
12 Diameter sel A
13 Diameter sel B
14 Tune/config input enable: Determines what is read from
network. “Read all” includes control/reference, tunable,
and configurable inputs
0=
READ ONLY CONTROL/REFERENCE INPUTS
1=READ ALL
15 Network sync
33 Network Reference Speed/voltage loop or
CML reference value when
CONTROL SOURCE SELECT (P.000) is set to NETWORK and
AMX NETW REF SELECT (P.911)=0
34
NETW IN REG 1 Written by network master. Read this value through the
OIM using NETW IN REG 1 (P.905)
35
NETW IN REG 2 Written by network master. Read this value through the
OIM using NETW IN REG 2 (P.906)
36
NETW IN REG 3 Written by network master. Read this value through the
OIM using nETW IN REG 3 (P.907)
37
TAPER REGISTER (P.860) Determines amount of taper to apply to the tension
reference when
TAPER TYPE (P.863) = REGISTER
0.000 to 1.000
38
FIELD REF REGISTER (P.513) Reference for the field current loop 4095 at MOTOR HOT FLD AMPS (P.510)
39
POSITION REFERENCE (P.240) Dancer position reference. -4095 to 4095 COUNTS
Table 7.5 – WebPak 3000 Register Map, Drop_1: Master Write Registers, BASIC and FULL Connections. Control/Reference Data (Drive Input Data) (Continued)
Register Bit Parameter Name (Number) Description Settings
Control/reference data are read by the regulator every 10 msec.