FlexPak 3000 Drives: Alternate Register Map
6-19
49 DIG OUT 2 SELECT (P.411) I/O Expansion kit digital output #2 source 0=LEVEL DETECT 1 OUTPUT (P.648); 1=LEVEL DETECT 2
OUTPUT (P.649); 2=in current limit; 3=drive ready; 4=NETW
COMM STATUS (P.908); 5=bit 1 of Network Input Register 1;
6=bit 1 of Network Input Register 2; 7=bit 1 of Network
Input Register 3
50 0
DIG OUT 1 CONTACT TYP (P.410) I/O Expansion kit digital output 1 contact type 0=NORMAL OPEN
1=NORMAL CLOSED
1 DIG OUT 2 CONTACT TYP (P.412) I/O Expansion kit digital output 2 contact type
51
ANLG IN 1 SIG TYPE (P.413) I/O Expansion kit analog input 1 signal type
0=0-10 V; 1=±10 V; 2=4-20mA; 3=10-50mA
52 ANLG OUT 1 SELECT (P.418) I/O Expansion kit analog output 1 source select See “Settings for Analog and Frequency Outputs” on
page 4-8
53
ANLG OUT 1 SIG TYPE (P.419) I/O Expansion kit analog output 1 signal type 0=0–10 V; 1=+/–10 V; 2=4-20 mA
54
ANLG OUT 2 SELECT (P.421) I/O Expansion kit analog output source select. See “Settings for Analog and Frequency Outputs” on
page 4-8
55
FREQ IN ZERO (P.423) I/O Expansion kit minimum input frequency kHz * 10
56
FREQ IN FULL SCALE (P.424) I/O Expansion kit maximum input frequency kHz * 10
57
FREQ OUT SELECT (P.425) I/O Expansion kit frequency output source select See “Settings for Analog and Frequency Outputs” on
page 4-8.
58
FREQ OUT ZERO (P.426) I/O Exp. kit frequency generated when frequency output
signal is zero
kHz * 10
59
FREQ OUT FULL SCALE (P.427) I/O Expansion kit frequency output at full scale kHz * 10
60
LEVEL DETECT 1 SELECT (P.602) Level detector 1 signal 0=CML FEEDBACK; 1=SPD LOOP FEEDBACK; 2=SPEED RAMP
OUTPUT; 3=SPD RAMP INPUT TP; 4=SPD SOURCE SELECT OUT
61 LEVEL DETECT 2 SELECT (P.605) Level detector 2 signal
62
NOMINAL AC LINE FREQ (P.306) Nominal AC line frequency Hz
63
NOMINAL AC LINE VOLTS (P.307) Nominal AC line RMS voltage volts RMS
Table 6.18 – FlexPak 3000 Alternate Register Map, Drop_4: Master Write Registers, FULL Connection. Configurable Data (Drive Input Data) (Continued)
Register Bit Parameter Name (Number) Description Settings
Configurable data are read by the regulator approximately every 600 msec when Tune/Config Input Enable bit=1 and the drive is not running or jogging.