AutoMax Network Communication Option Board
Table 6.17 – FlexPak 3000 Alternate Register Map, Drop_4: Master Write Registers FULL Connection. Tunable Data (Drive Input Data),
Register Bit Parameter Name (Number) Description Settings
32 ANLG IN 1 ZERO ADJ (P.414) I/O Expansion kit analog input 1 zero adjust
33
ANLG IN 1 GAIN ADJ (P.415) I/O Expansion kit analog input 1 gain adjust gain * 1000
34
ANLG IN 2 ZERO ADJ (P.416) I/O Expansion kit analog input 2 zero adjust
35
ANLG IN 2 GAIN ADJ (P.417) I/O Expansion kit analog input 2 gain adjust gain * 1000
36
LEVEL DETECT 1 THRESH (P.603) Level detector 1 threshold % * 10
37
LEVEL DETECT 1 DELAY (P.604) Level detector 1 delay time seconds * 10
38
LEVEL DETECT 2 THRESH (P.606) Level detector 2 threshold % * 10
39
LEVEL DETECT 2 DELAY (P.607) Level detector 2 delay time seconds * 10
40
PLL MAXIMUM ERROR (P.308) Max. allowed change in line period per AC line cycle µsec
41
ENHANCED FLD VOLT ADJ (P.500) Adjusts the field output voltage
42
FIELD ECONOMY DELAY (P.501) Time between stopping and entering field economy minutes
43
OPEN SCR SENSITIVITY (P.600) Open SCR detection sensitivity adjustment
44
OPEN SCR TRIP THRESH (P.601) Open SCR detection trip threshold
45
ANLG OUT 1 GAIN ADJ (P.420) I/O Expansion kit analog output 1 gain adjust gain * 1000
46
ANLG OUT 2 GAIN ADJ (P.422) I/O Expansion kit analog output 2 gain adjust gain * 1000
Tunable data are read by the regulator approximately every 600 msec when Tune/Config Input Enable bit = 1
Table 6.18 – FlexPak 3000 Alternate Register Map, Drop_4: Master Write Registers, FULL Connection. Configurable Data (Drive Input Data)
Register Bit Parameter Name (Number) Description Settings
47 DIG IN 0 SELECT (P.428) Determines the function controlled by digital input 0 0=BRUSH WEAR INPUT;1=JOG SPEED SELECT; 2=OCL ENABLE
48 DIG OUT 1 SELECT (P.409) I/O Expansion kit digital output 1 source 0=LEVEL DETECT 1 OUTPUT (P.648)
1=
LEVEL DETECT 2 OUTPUT (P.649)
2=in current limit; 3=drive ready
4=
NETW COMM STATUS (P.908)
5=bit 0 of Network Input Register 1
6=bit 0 of Network Input Register 2
7=bit 0 of Network Input Register 3
Configurable data are read by the regulator approximately every 600 msec when Tune/Config Input Enable bit=1 and the drive is not running or jogging.