User Manual

FlexPak 3000 Drives: Alternate Register Map
6-17
54 AUTO REFERENCE SELECT (P.103) Selects the type of auto reference 0= ANALOG; 1=FREQUENCY IN
55 MOTOR HOT FLD AMPS (P.510) Rated hot field amps from motor nameplate amps * 100
56
FIELD LOSS THRESHOLD (P.512) Field current level at which a field loss fault is generated % of MOTOR HOT FLD AMPS (P.510)
57
FIELD AUTO WEAKEN (P.517) Enables or disables automatic field weakening 0=DISABLED; 1=ENABLED
58 MAXIMUM CURRENT (P.007) Highest amount of current, either positive or negative % of MOTOR RATED ARM AMPS (P.008)
59
MOTOR RATED ARM AMPS (P.008) Rated armature current from motor nameplate amps * 10
60
MOTOR RATED ARM VOLTS (P.009) Rated armature voltage from motor nameplate volts DC
61
ANLG TACH VOLTS/1000 (P.203) Analog tach scaling from tach nameplate in V/1000 RPM volts * 10
62
PULSE TACH PPR (P.207) Pulses per revolution from pulse encoder nameplate
63
PULSE TACH QUADRATURE (P.208) Enables or disables pulse encoder quadrature 0=OFF; 1=ON (quad decode)
Table 6.16 – FlexPak 3000 Alternate Register Map, Drop_4: Master Read Registers, FULL Connection. Tunable, Configurable, and Status Data (Drive Output Data)
Register Bit Parameter Name (Number) Description Settings
23 NOMINAL AC LINE FREQ (P.306) Nominal AC line frequency Hz
24 Reserved
25
PLL MAXIMUM ERROR (P.308) Max. allowed change in line period per AC line cycle µsec
26 Reserved
27
ENHANCED FLD VOLT ADJ (P.500) Adjusts the field output voltage
28
FIELD ECONOMY DELAY (P.501) Time between stopping and entering field economy minutes
29
FIELD ECONOMY ACTIVE (P.599) Indicates the present state of field economy 0=OFF; 1=ON (field economy active)
30
OPEN SCR SENSITIVITY (P.600) Open SCR detection sensitivity adjustment
31
OPEN SCR TRIP THRESH (P.601) Open SCR detection trip threshold
Tunable, configurable, and status data are updated by the regulator approximately every 600 msec.
Table 6.15 – FlexPak 3000 Alternate Register Map, Drop_3: Master Write Registers, FULL Connection. Configurable Data (Drive Input Data) (Continued)
Register Bit Parameter Name (Number) Description Settings
Configurable data are read by the regulator approximately every 600 msec when Tune/Config Input Enable bit=1 and the drive is not running or jogging.