User Manual
6-6
AutoMax Network Communication Option Board
1 (con’t.) 13 Terminal strip auto/manual
14 Digital input 0
15 Motor thermostat
2
SPD LOOP REFERENCE (P.295) Final speed/voltage loop reference value 4095 at TOP SPEED (P.011)
3
SPD LOOP FEEDBACK (P.296) Final speed/voltage loop feedback value after all scaling 4095 at TOP SPEED (P.011)
4
SPD LOOP OUTPUT (P.299) Speed loop PI block output value 4095 at MAXIMUM CURRENT (P.007)
5
ARMATURE VOLTAGE (P.289) Armature voltage feedback value 4095 at MOTOR RATED ARM VOLTS (P.009)
6Average
CML feedback Current minor loop feedback average over 8 CML scans 4095 at MAXIMUM CURRENT (P.007)
7 Network Output Register 1 Value of the parameter selected by
NETW OUT REG 1
SELECT (P.902)
If no valid parameter value selected,
0=motor speed in RPM
8 Network Output Register 2 Value of the parameter selected by NETW OUT REG 2
SELECT (P.903)
If no valid parameter value selected,
0=armature voltage in volts
9 Network Output Register 3 Value of the parameter selected by
NETW OUT REG 3
SELECT (P.904)
If no valid parameter value selected,
0=armature current in amps*10 or amps
10 to 15 Tunable, Configurable and Status Data See table 6.4 on page 6-7.
16
ANALOG AUTO REFERENCE (P.188) Analog reference value in auto mode after all scaling 4095 at TOP SPEED (P.011)
17
ANALOG MAN TRIM REF (P.194) Analog manual trim reference input value 4095 at TOP SPEED (P.011)
18
ANLG IN 1 (P.492) I/O Exp. kit analog input 1 after gain and zero applied 4095 at full scale
19
ANLG IN 2 (P.493) I/O Exp. kit analog input 2 after gain and zero applied 4095 at full scale
20
FREQ IN (P.491) I/O Expansion kit frequency input value after all scaling 4095 at full scale
21
OCL OUTPUT (P.848) Outer control loop output value RPM
22 FIELD FEEDBACK (P.589) Motor field current feedback value after scaling and gain 4095 at MOTOR HOT FLD AMPS (P.510)
23
AC LINE VOLTAGE (P.392) Measured AC line RMS voltage volts RMS
*
The I/O Expansion kit digital inputs do not have fixed functions when CONTROL SOURCE SELECT (P.000) is set to NETWORK. Therefore, they do not select preset speeds, change the MOP
setpoint, or enable or disable the
OCL.
Table 6.3 – FlexPak 3000 Alternate Register Map, Drop_1: Master Read Registers, BASIC and FULL Connections. Runtime Signal Data (Drive Output Data) (Continued)
Register Bit Parameter Name (Number) Description Settings
Runtime signal data are updated by the regulator every 5 msec, unless FEEDBACK SELECT (P.200) is set to ARMATURE VOLT, in which case the update time is 10 msec.