User Manual
FlexPak 3000 Drives: Original Register Map
5-15
22 Stop cause word Bit-packed word indicating why the drive stopped
0 Stop asserted or Run de-asserted (negated)
1 Jog de-asserted for less than 1 second
2 Internal stop request
3 Current limit stop
4 Ramp stop
5 Coast/DB stop
6 Fault stop or self-tuning complete
7 Customer interlock opened
8 Coast/DB interlock opened
9 Main contactor opened
10 – 15 Reserved
23
NOMINAL AC LINE FREQ (P.306) Nominal AC line frequency Hz
24
NOMINAL AC LINE VOLTS (P.307) Nominal AC line RMS voltage volts RMS
25 PLL MAXIMUM ERROR (P.308) Max. allowed change in line period per AC line cycle µsec
26
AC LINE VOLTAGE (P.392) Measured AC line RMS voltage volts RMS
27 ENHANCED FLD VOLT ADJ (P.500) Adjusts the field output voltage
28
FIELD ECONOMY DELAY (P.501) Time between stopping and entering field economy minutes
29
FIELD ECONOMY ACTIVE (P.599) Indicates the present state of field economy 0=OFF; 1=ON (field economy active)
30
OPEN SCR SENSITIVITY (P.600) Open SCR detection sensitivity adjustment
31
OPEN SCR TRIP THRESH (P.601) Open SCR detection trip threshold
Table 5.16 – FlexPak 3000 Original Register Map, Drop_4: Master Read Registers, FULL Connection. Tunable, Configurable, and Status Data (Drive Output Data) (Continued)
Register Bit Parameter Name (Number) Description Settings
Tunable, configurable and status data are updated by the regulator approximately every 600 msec.