Table 5.15 – FlexPak 3000 Original Register Map, Drop_4: Master Read Registers, FULL Connection. Runtime Signal Data (Drive Output Data)
Register Bit Parameter Name (Number) Description Settings
0 I/O Expansion kit digital inputs
Bit-packed word that indicates the state of these inputs
*
*
The I/O Expansion kit digital inputs do not have fixed functions when CONTROL SOURCE SELECT (P.000) is set to NETWORK. Therefore, they do not select preset speeds,
change the
MOP setpoint, or enable or disable the OCL.
0 I/O Expansion kit digital input 1 (Preset speed select 1)*
1 I/O Expansion kit digital input 2 (Preset speed select 2)*
2 I/O Expansion kit digital input 3 (mop decrement)*
3 I/O Expansion kit digital input 4 (mop increment)*
4 I/O Expansion kit digital input 5 (ocl enable)*
1
ANLG IN 1 (P.492) I/O Exp. kit analog input 1 after gain and zero applied 4095 at full scale
2
ANLG IN 2 (P.493) I/O Exp. kit analog input 2 after gain and zero applied 4095=full scale
3
FREQ IN (P.491) I/O Expansion kit frequency input value after all scaling 4095=full scale
4 to 20 Reserved
Runtime signal data are updated by the regulator every 5 msec, unless
FEEDBACK SELECT (P.200) is set to ARMATURE VOLT, in which case the update time is 10 msec.
Table 5.16 – FlexPak 3000 Original Register Map, Drop_4: Master Read Registers, FULL Connection. Tunable, Configurable, and Status Data (Drive Output Data)
Register Bit Parameter Name (Number) Description Settings
21 Level Detector Outputs Bit-packed word indicating state of level detector outputs
0 Level detector 1 output
1 Level detector 2 output
Tunable, configurable and status data are updated by the regulator approximately every 600 msec.