User Manual

5-6
AutoMax Network Communication Option Board
Table 5.4 – FlexPak 3000 Original Register Map, Drop_1: Master Write Registers, BASIC and FULL Connections. Control/Reference Data (Drive Input Data)
Register Bit Parameter Name (Number) Description Settings
32 Sequencing control word Word containing drive sequencing and control bits
0 Run 0 to 1 transition to run
1 Stop 0=stop; 1=not stop
2 Fault reset 0 to 1 transition to reset
3 Jog 0 to 1 transition to jog; 0=stop jogging
4 Forward/reverse select 0=forward; 1=reverse
5 to 6 Reserved
7 Outer control loop enable 0=hold
OCL in reset; 1=OCL enabled
8 Fault log clear and reset 0 to 1 transition to clear
9 Alarm log clear and reset 0 to 1 transition to clear
10 Alarm reset 0 to 1 transition to reset
11 Memory save 0 to 1 transition to save
12 – 13 Reserved
14 Tune/config input enable: Determines what is read from
network. “Read all” includes control/reference, tunable,
and configurable inputs
0=read only control/reference inputs
1=read all
15 Tune/config update synchronization flag (master write)
33 Network Reference Speed/voltage loop or
CML reference value when
CONTROL SOURCE SELECT (P.000) is set to NETWORK and
AMX NETW REF SELECT (P.911)=0
4095 at
TOP SPEED (P.011)/MOTOR RATED
ARM VOLTS (P.009) or MAXIMUM CURRENT
(P.007)
34 Network Input Register 1 Written by network master. Read this value through the
OIM or DCM using NETW IN REG 1 (P.905)
35 Network Input Register 2 Written by network master. Read this value through the
OIM or DCM using NETW IN REG 2 (P.906)
36 Network Input Register 3 Written by network master. Read this value through the
OIM or DCM using NETW IN REG 3 (P.907)
37
FIELD REF REGISTER (P.513) Reference for the field current loop 4095 at MOTOR HOT FLD AMPS (P.510)
38 to 39 Reserved
Control/reference data are read by the regulator every 5 msec, unless
FEEDBACK SELECT (P.200) is set to ARMATURE VOLT, in which case the update time is 10 msec.