User Manual
5-4
AutoMax Network Communication Option Board
Table 5.3 – FlexPak 3000 Original Register Map, Drop_1: Master Read Registers, BASIC and FULL Connections. Tunable, Configurable, and Status Data (Drive Output Data)
Register Bit Parameter Name (Number) Description Settings
10 Fault latch bits word 1 Bit-packed word indicating latched faults
0
AC LINE SYNCHRONIZATION FAULT (F00010)
1
FIELD CURRENT LOSS (F00004)
2
SUSTAINED OVERLOAD (F00005)
3
SELF TUNING FAULT (F00060 to F000099)
4
MOTOR THERMOSTAT TRIP (F00008)
5
CONTROLLER THERMOSTAT TRIP (F00009)
6
BLOWER MOTOR STARTER OPEN (F00006)
7 Reserved
8
IET (OVERCURRENT) (F00001)
9
OVERSPEED (F00003) / ARMATURE OVERVOLTAGE
(F00012)
10
SCR
N
or
MULTIPLE
SCRS
NOT
OPERATING
(F00030–F00042)
11 OPEN ARMATURE (F00007)
12
TACHOMETER LOSS (F00002)
13
OIM COMMUNICATIONS TIMEOUT (F00011)
14
NETWORK COMMUNICATION TIMEOUT (F00013)
15
REVERSED TACH LEADS (F00014)
11 Reserved
12 First fault Fault code of the first fault since the last fault reset
13 Alarm latch bits word Bit-packed word containing latched alarm bits
0
MOTOR BRUSH WEAR LOW (A00001)
1
AC LINE VOLTAGE LOW (A00002)
2
AC LINE VOLTAGE HIGH (A00003)
3 to 15 Reserved
14 Last alarm Alarm code of the most recent alarm
15
CONTROL SOURCE SELECT (P.000) Selected source for drive control signals
0=
TERMBLK
; 1=
KEYPAD
; 2=
SERIAL
; 3=
NETWORK
16 ACCELERATION TIME (P.001) Min. time to accelerate from zero to TOP SPEED (P.011) seconds * 10
17
DECELERATION TIME (P.002) Min. time to decelerate from TOP SPEED (P.011) to zero seconds * 10
Tunable, configurable, and status data are updated by the regulator approximately every 600 msec.