FlexPak 3000 DC Drive Software Reference
F00009
CONTROLLER
THERMOSTAT
TRIP
Drive thermostat indicates high temperature (>50°C)
Possible causes:
Inadequate heat sink ventilation.
Inadequate cabinet ventilation.
Heat sink fan failure.
Damaged or disconnected drive thermostat wiring.
F00010
AC
LINE
SYNCHRONIZATION
FAULT
Three-phase AC line synchronization circuit failure.
Possible causes:
Blown AC line fuse(s).
AC line frequency not within required range of 48 to 62Hz.
Excessive AC line noise or distortion.
Unstable AC line frequency. See
PLL
MAXIMUM
ERROR
(P.308).
Disconnected, loosely connected or damaged J6 ribbon cable.
F00011
OIM
COMMUNICATIONS
TIMEOUT
The Regulator board was unable to communicate with the interface
module (
OIM
or
DCM
). (See the hardware manual for a description of
regulator status
LED
s that can pinpoint whether or not the interface module
is communicating.)
Possible causes:
Disconnected, loosely connected, or damaged interface module/serial
cable.
Regulator board failure.
F00012
ARMATURE
OVER
VOLTAGE
Armature voltage exceeded 125% of
MOTOR
RATED
ARM
VOLTS
(P.009).
Possible causes:
MOTOR
RATED
ARM
VOLTS
not set properly.
Improper voltage loop tuning.
ENHANCED
FLD
VOLT
ADJ
(P.500) set too high (Enhanced Field Supply kit
only).
F00013
NETWORK
COMMUNICATION
TIMEOUT
Network communications is missing or failed to communicate with master
(
CONTROL
SOURCE
SELECT
set to
NETWORK
).
Possible causes:
NETW
CONNECT
TYPE
(P.910) was changed from
BASIC
to
FULL
.
NETW
DROP
NUMBER
(P.900) was changed.
Network option cable connections are loose or not connected.
Network option board failed or master communications failed.
Table 13.1 – Fault Codes (Continued)
Code OIM Display Description