User guide

Troubleshooting the FlexPak 3000 Drive
13-3
F00005
SUSTAINED
OVERLOAD
Inverse time overload circuit trip.
Possible causes:
Incorrect armature current feedback scaling (
MOTOR
RATED
ARM
AMPS
,
MAXIMUM
CURRENT
,
CT
TURNS
RATIO
, and/or J18 not set properly).
Blown field supply fuse(s).
Mechanical binding preventing the motor shaft from rotating freely.
F00006
BLOWER
MOTOR
STARTER
OPEN
The blower motor starter is open. If a blower motor starter kit is not
installed, connector P8 must be fitted with the proper substitute connector
to inhibit this fault.
Possible causes:
Blown blower motor starter fuse(s).
Disconnected, loosely connected, or damaged blower motor starter
wiring.
Blower motor overload.
F00007
OPEN
ARMATURE
The motor armature circuit is open.
Possible causes:
Motor armature winding not connected or open circuit.
Blown inverting fault (DC) fuse.
Inverting fault breaker tripped.
F00008
MOTOR
THERMOSTAT
TRIP
Motor thermostat indicates high temperature. If a motor thermostat is not
used, customer terminal board pins 13 and 14 must be jumpered to inhibit
this fault.
Possible causes:
Damaged or disconnected motor thermostat wiring.
Inadequate ventilation.
Blower motor failure.
Incorrect blower rotation.
Blocked ventilation slots.
Clogged filters.
Excessive armature current.
One or more thyristors not operating.
Table 13.1 – Fault Codes (Continued)
Code OIM Display Description