User guide

Register Map for WebPak 3000 Drives
8-19
N11:20 SPEED CROSS OVER P.133 Speed loop cross over frequency
N11:21
SPEED PI WLD OUT P.250 Value of the speed loop PI low frequency
N11:22
SPEED PI KP OUT P.251 Value of the speed loop PI proprotional gain
N11:23
SPEED LAG FREQ OUT P.252 Value of the speed loop lag frequency
N11:24
DRAW PERCENTAGE OUT P.196 Product of selected trim reference and TRIM RANGE
(P.109)
N11:25
TRIM OUTPUT P.197 Present value added to SPD SOURCE SELECT OUt
(P.193)
N11:26
SPEED RAMP INPUT TP P.198 Speed reference value immediately before S-CURVE
ramp.
N11:27
SPEED RAMP OUTPUT P.199 Speed reference value immediately after S-curve
ramp
N11:28
INSTANTANEOUS INERTIA P.230 Calculated value of the dynamic load inertia as
provided by the inertia compensation task
N11:29
INERTIA COMPENSATION P.244 Output of the inertia compensation calculator
N11:30
LOSSES COMPENSATION P.316 Output of the losses compensation calculator
N11:31
IR COMPENSATION TP P.290 Value subtracted from ARMATURE VOLTAGE (P.289)
N11:32
ANALOG TACH FEEDBACK P.291 Analog tachometer value after scaling
N11:33
ENCODER FEEDBACK P.292 Encoder value after scaling
N11:34
CURRENT COMPOUND TP P.293 Value subtracted from SPEED RAMP OUTPUT (P.199)
N11:35
JOG RAMP OUTPUT P.294 Jog reference value immediately after jog ramp
N11:36
SPD LOOP ERROR P.297 Difference between SPD LOOP REFERENCE (P.295) and
SPD LOOP FEEDBACK (P.296)
N11:37
SPD LOOP LAG OUTPUT P.298 Value immediately after speed loop forward path lag
N11:38
CML RAMP INPUT TP P.390 Current reference value to the CML ramp block
N11:39
CML SPEED REFERENCE P.391 Speed reference value to the current minor loop
N11:40
AC LINE VOLTAGE P.392 Measured AC line voltage (RMS value)
N11:41
AC LINE PERIOD P.393 Measured AC line period (µsec)
N11:42
ARMATURE BRIDGE POL P.394 0 = OFF (forward bridge active)
1 =
ON (reverse bridge active)
N11:43
J18 ARM I FB RESISTOR P.395 1 = 15 ohm, 2 = 20 ohm, 3 = 30 ohm, 4 = 39 ohm
N11:44
CML REFERENCE P.396 Reference value to the CML after rate and amplitude
limiting
N11:45
CML FEEDBACK
(10 ms update)
P.397 CML feedback value after conditioning and scaling
N11:46
CML ERROR P.398 Difference between CML REFERENCE (P.396) and CML
FEEDBACK (P.297)
N11:47
ARMATURE DELTA P.399 Present armature firing angle in µsec
N11:48
UNDERWIND DIN TP P.490 0 = OFF, 1 = ON
N11:49 UNDERWIND COMMAND P.877 0 = OFF, 1 = ON
N11:50 FREQ IN P.491 Frequency input (terminals 39, 40, 41 on the I/O
Expansion board)
Table 8.2 – File N11:x (Drive Display Data (Read Only)) for WebPak 3000 Drives (Continued)
File
Address Parameter Name
Parameter
Number Description