User guide
8-18
ControlNet Network Communication Option Board For Use With FlexPak 3000 and WebPak 3000 DC Drives
N11:9 Network Output Reg 3 --- Value of parameter from NETW OUT REG 3 SELECT
(P.904)
N11:10
NETW IN REG 1 P.905 Present value of Network Input Register 1
N11:11
NETW IN REG 2 P.906 Present value of Network Input Register 2
N11:12
NETW IN REG 3 P.907 Present value of Network Input Register 3
N11:13 Drive Fault Word 1
(latched)
--- b00 Line Synchronization Loss
b01 Field Current Loss
b02 Sustained Overload
b03 Self Tune
b04 Motor Thermostat
b05 Controller Thermostat
b06 Blower Motor Starter Open
b07 Shorted SCR
b08 Instantaneous Overcurrent
b09 Overspeed/Overvoltage
b10 Open SCR
b11 Open Armature
b12 Tachometer Loss
b13 OIM Communication
b14 Network Communication
b15 Tracking (reversed tach) Error
N11:14 Drive Fault Word 2
(latched)
--- Reserved
N11:15 Drive Alarm Word
(latched)
--- b00 Reserved
b01 AC line voltage low (<90%)
b02 AC line voltage high (>115%)
b03 Reserved
|
b15 Reserved
N11:16 Drive Stop Cause Word --- b00 Stop asserted
b01 Jog de-asserted for > 1 second
b02 Internal stop request
b03 Current Limit stop
b04 Ramp stop
b05 Coast/DB stop
b06 Fault stop (or self tune completed)
b07 Customer Interlock opened
b08 Coast/DB Interlock opened
b09 Main contactor opened
b10 Reserved
|
b15 Reserved
N11:17
LINE SPEED P.188 Analog reference value output by the drive after
scaling
N11:18
TORQUE REFERENCE P.189 Present torque (current) reference value
N11:19
SPD SOURCE SELECT OUT P.193 Selected speed source value
Table 8.2 – File N11:x (Drive Display Data (Read Only)) for WebPak 3000 Drives (Continued)
File
Address Parameter Name
Parameter
Number Description