User guide
8-6
ControlNet Network Communication Option Board For Use With FlexPak 3000 and WebPak 3000 DC Drives
N10:129 SELF TUNE BRIDGE P.220 Tunable 0 = FORWARD, 1 = REVERSE
N10:130 OPEN SCR SENSITIVITY P.600 Tunable 1 = 1%
N10:131
OPEN SCR TRIP THRESH P.601 Tunable
N10:132 Clock Functions Read = Elapsed time (hours) since last
power up.
Write bit 0 = 1 Reset clock to zero; any
other value written has no effect.
N10:133
|
N10:149
Reserved --- --- Reserved (future parameter expansion)
N10:150
CONTROL SOURCE SELECT P.000 Config 0 = TERMBLK
1 =
KEYPAD
2 =
SERIAL
3 =
NETWORK
N10:151 CNI PROG/RUN MODE P.915 Config 0 = STOP
1 = USE LAST REF
N10:152 MOTOR RATED ARM AMPS P.008 Config 1 = 0.1 amp
N10:153
MOTOR RATED ARM VOLTS P.009 Config 1 = 1 volt
N10:154
MAXIMUM CURRENT P.007 Config 1 = 1% of MOTOR RATED ARM AMPS (P.008)
N10:155
CML REF LIMIT SELECT P.311 Config 0 = SPD LOOP PI LIMITS, 1 = REGISTER
N10:156 GEAR IN SPEED P.011 Config 1 = 1 RPM
N10:157 TOP LINE SPEED P.020 Config 1 = 1 FPM
N10:158 BASE SPEED P.017 Config 1 = 1 RPM
N10:159 GEARING P.019 Config 1 = 0.01
N10:160
REVERSE DISABLE P.015 Config 0 = OFF, 1 = ON
N10:161 LINE SPEED REF SELECT P.103 Config 0 = ANALOG, 1 = FREQUENCY IN
N10:162 INERTIA COMP SELECT P.221 Config 0 = NONE
1 = CALCULATOR
2 = NETW IN REG 1
3 =
NETW IN REG 2
4 =
NETW IN REG 3
N10:163
DIAMETER UPDATE RATE P.867 Config 1 = 1 revolution
N10:164
BUILDUP CONSTANT P.871 Config 1 = 0.001
N10:165
LOSSES COMP SELECT P.315 Config 0 = NONE
1 = CALCULATOR
2 = NETW IN REG 1
3 =
NETW IN REG 2
4 =
NETW IN REG 3
N10:166
POS CURRENT LIM SEL P.223 Config 0 = REGISTER
1 = PARALLEL OCL
2 = NETW IN REG 1
3 =
NETW IN REG 2
4 =
NETW IN REG 3
Table 8.1 – File N10:x (Drive Read/Write Parameters) for WebPak 3000 Drives (Continued)
File
Address Parameter Name
Parameter
Number Type Scale