User guide

7-14
ControlNet Network Communication Option Board For Use With FlexPak 3000 and WebPak 3000 DC Drives
N11:47 DIG IN 2 P.496 Digital input 2 (terminal 60 on the I/O Expansion
board) Preset B
N11:48
DIG IN 3 P.497 Digital input 3 (terminal 62 on the I/O Expansion
board) MOP decrease
N11:49
DIG IN 4 P.498 Digital input 4 (terminal 63 on the I/O Expansion
board) MOP increase
N11:50
DIG IN 5 P.499 Digital input 5 (terminal 64 on the I/O Expansion
board) OCL Enable
N11:51
FLD CURRENT REGULATOR P.586 0 = NOT INSTALLED
1 = 4 amp
2 = 10 amp
3 = 20 amp
N11:52
FIELD DELTA P.588 Field firing angle in deg
N11:53
FIELD FEEDBACK
(5 OR 10 MS UPDATE)
P.589 Motor field feedback value
N11:54
FIELD REFERENCE P.590 Field current reference value
N11:55
J20 FIELD LOSS DETECT P.597 0 = ENABLED, 1 = DISABLED
N11:56 J21 FLD SUPPLY JUMPER P.598 0 = B-C, 1 = A-C
N11:57 FIELD ECONOMY ACTIVE P.599 0 = OFF, 1 = ON
N11:58 LEVEL DETECT 1 OUTPUT P.648 0 = OFF, 1 = ON
N11:59 LEVEL DETECT 2 OUTPUT P.649 0 = OFF, 1 = ON
N11:60 J11 ANLG TACH VLT SCL P.792 0 = 16
1 = 31/125
2 = 62/250
N11:61
J14 ANLG TACH VLT RNG P.793 0 = LOW, 1 = HIGH
N11:62 REGULATOR SW VERSION P.794 V.VV, Regulator board firmware version number
N11:63
POWER UNIT TYPE P.795 0 = S6R (Regen), 1 = S6 (Non-Regen)
N11:64
NETWORK KIT P.796 0 = NOT INSTALLED
1 =
INSTALLED
2 =
FAILED DIAGS
N11:65 I/O EXPANSION KIT P.797 0 = NOT INSTALLED
1 =
INSTALLED
2 =
FAILED DIAGS
N11:66 PULSE TACHOMETER KIT P.798 0 = NOT INSTALLED
1 =
INSTALLED
2 =
FAILED DIAGS
N11:67 J15 REGULATOR TYPE P.799 0 = SPEED/VOLTAGE, 1 = CURRENT/TORQUE
N11:68 OCL REFERENCE P.845 OCL reference value
N11:69
OCL RAMP OUTPUT P.846 OCL reference value immediately after OCL ramp
N11:70
OCL FEEDBACK P.847 OCL feedback value
N11:71
OCL OUTPUT P.848 OCL output value added to SPEED RAMP OUTPUT
(P.199)
N11:72
OCL ENABLE P.849 0 = OFF, 1 = ON
Table 7.2 – File N11:x (Drive Display Data (Read Only)) for FlexPak 3000 Drives (Continued)
File
Address Parameter Name
Parameter
Number Description