User guide

Register Map for FlexPak 3000 Drives
7-7
N10:166 ANLG TACH VOLTS/1000 P.203 Config 1 = 0.1 volts/1000 RPM
N10:167 PULSE TACH PPR P.207 Config 1 = 1 PPR
N10:168 PULSE TACH QUADRATURE P.208 Config 0 = OFF, 1 = ON
N10:169 OCL PROP TRIM SELECT P.813 Config 0 = DISABLED, 1 = ENABLED
N10:170 OCL FEEDBACK SELECT P.804 Config 0 = NONE
1 =
CML FEEDBACK
2 = ANALOG IN 1
3 =
ANALOG IN 2
4 =
SPEED LOOP OUTPUT
5 =
ANALOG AUTO REFERENCE
6 = NETW IN REG 1
7 =
NETW IN REG 2
8 =
NETW IN REG 3
N10:171
OCL TYP3 POSN REG P.814 Config 0 = DISABLED, 1 = ENABLED
N10:172 MOTOR HOT FLD AMPS P.510 Config 1 = 0.01 amp
N10:173
FIELD REF SELECT P.521 Config 0 = REGISTER
1 =
ANALOG MAN TRIM REF
2 = ANALOG IN 1
3 =
ANALOG IN 2
N10:174
FIELD DELTA HIGH LIM P.587 Config 1 = 1 deg
N10:175
FIELD LOSS THRESHOLD P.512 Config 1 = 1% of MOTOR HOT FLD AMPS (P.510)
N10:176
FIELD AUTO WEAKEN P.517 Config 0 = DISABLE, 1 = ENABLE
N10:177 CT TURNS RATIO P.010 Config
N10:178
MOP RESET ENABLE P.116 Config 0 = OFF, 1 = ON
N10:179 JOG OFF DELAY TIME P.121 Config 1 = 0.1 s
N10:180
STOP DECEL SELECT P.122 Config 0 = DECELERATION TIME
1 =
RAMP STOP DECEL TIME
N10:181 NOMINAL AC LINE FREQ P.306 Config 1 = 1 Hz
N10:182
NOMINAL AC LINE VOLTS P.307 Config 1 = 1 VAC
N10:183 PHASE LOSS DETECT EN P.609 Config 0 = DISABLE, 1 = ENABLE
N10:184 DIG OUT 1 SELECT P.409 Config 0 = LEVEL DETECT 1 OUTPUT
1 =
LEVEL DETECT 2 OUTPUT
2 = IN CURRENT LIMIT
3 =
DRIVE READY
4 = NETW COMM STATUS
5 =
NETW IN REG 1 (BIT 0)
6 =
NETW IN REG 2 (BIT 0)
7 =
NETW IN REG 3 (BIT 0)
N10:185
DIG OUT 1 CONTACT TYP P.410 Config 0 = NORMAL OPEN
1 =
NORMAL CLOSED
Table 7.1 – File N10:x (Drive Read/Write Parameters) for FlexPak 3000 Drives (Continued)
File
Address Parameter Name
Parameter
Number Type Scale