User guide
Register Map for FlexPak 3000 Drives
7-5
N10:82 METER OUT 2 SELECT P.405 Tunable 0 = CML FEEDBACK
1 =
CML REFERENCE
2 =
CML ERROR
3 =
SPD LOOP FEEDBACK
4 = SPD LOOP REFERENCE
5 =
SPD LOOP ERROR
6 = SPD LOOP OUTPUT
7 =
SPEED RAMP OUTPUT
8 = SPEED RAMP INPUT TP
9 =
SPD SOURCE SELECT OUT
10 = TRIM OUTPUT
11 =
ARMATURE VOLTAGE
12 =
ANALOG TACH FEEDBACK
13 =
PULSE TACH FEEDBACK
14 =
ZERO
15 =
FULL SCALE
16 = POWER OUTPUT
17 =
OCL REFERENCE
18 = OCL RAMP OUTPUT
19 =
OCL FEEDBACK
20 = OCL OUTPUT
21 =
FIELD REFERENCE
22 = FIELD FEEDBACK
23 =
NETW IN REG 1
24 =
NETW IN REG 2
25 =
NETW IN REG 3
N10:83
ANLG OUT 1 GAIN ADJ P.420 Tunable 1 = 0.001
N10:84
ANLG OUT 2 GAIN ADJ P.422 Tunable 1 = 0.001
N10:85
LEVEL DETECT 1 THRESH P.603 Tunable 1 = 0.1% of selected source
N10:86
LEVEL DETECT 1 DELAY P.604 Tunable 1 = 0.1 s
N10:87
LEVEL DETECT 2 THRESH P.606 Tunable 1 = 0.1% of selected source
N10:88
LEVEL DETECT 2 DELAY P.607 Tunable 1 = 0.1 s
N10:89
PLL MAXIMUM ERROR P.308 Tunable 1 = 1 µsec
N10:90
TACH LOSS SCR ANGLE P.608 Tunable 1 = 1 deg
N10:91
TACH LEAD FLT THRESH P.227 Tunable 1 = 0.1% of TOP SPEED (P.011)
N10:92
TACH LEAD FLT DELAY P.228 Tunable 1 = 1 ms
N10:93
SELF TUNE FIELD RANGE P.218 Tunable 1 = 0.01
N10:94
SELF TUNE STABILITY P.219 Tunable
N10:95
SELF TUNE BRIDGE P.220 Tunable 0 = FORWARD, 1 = REVERSE
N10:96
OPEN SCR SENSITIVITY P.600 Tunable 1 = 1%
N10:97
OPEN SCR TRIP THRESH P.601 Tunable
N10:98
CLOCK FUNCTIONS --- Tunable Read = Elapsed time (hours) since last
power up
Write bit 0 = 1 Reset clock to zero; any
other value written has no effect.
Table 7.1 – File N10:x (Drive Read/Write Parameters) for FlexPak 3000 Drives (Continued)
File
Address Parameter Name
Parameter
Number Type Scale