User guide
Register Map for FlexPak 3000 Drives
7-3
N10:57 TRIM REFERENCE SELECT P.108 Tunable 0 = REGISTER
1 = ANALOG MANUAL
2 = ANALOG IN 1
3 =
NETW IN REG 1
4 =
NETW IN REG 2
5 =
NETW IN REG 3
6 =
ANALOG IN 2
N10:58
TRIM RANGE P.109 Tunable 1 = 0.1%
N10:59
TRIM MODE SELECT P.110 Tunable 0 = NO TRIM
1 =
INCREMENTAL
2 =
PROPORTIONAL
N10:60 MOP ACCEL TIME P.115 Tunable 1 = 0.1 s
N10:61
MOP DECEL TIME P.120 Tunable 1 = 0.1 s
N10:62
PRESET SPEED 1 P.117 Tunable 1 = 1 RPM
N10:63 PRESET SPEED 2 P.118 Tunable 1 = 1 RPM
N10:64 PRESET SPEED 3 P.119 Tunable 1 = 1 RPM
N10:65 ANALOG TACH GAIN ADJ P.201 Tunable 1 = 0.001
N10:66
ANALOG TACH ZERO ADJ P.202 Tunable
N10:67
ARM VOLTAGE GAIN ADJ P.204 Tunable 1 = 0.001
N10:68
ARM VOLTAGE ZERO ADJ P.205 Tunable
N10:69
ANLG AUTO GAIN ADJ P.101 Tunable 1 = 0.001
N10:70
ANLG AUTO ZERO ADJ P.102 Tunable
N10:71
ANLG MAN REF GAIN ADJ P.104 Tunable 1 = 0.001
N10:72
ANLG MAN REF ZERO ADJ P.105 Tunable
N10:73
ANLG IN 1 GAIN ADJ P.415 Tunable 1 = 0.001
N10:74
ANLG IN 1 ZERO ADJ P.414 Tunable
N10:75
ANLG IN 2 GAIN ADJ P.417 Tunable 1= 0.001
N10:76
ANLG IN 2 ZERO ADJ P.416 Tunable
N10:77
METER OUT 1 GAIN ADJ P.400 Tunable 1= 0.001
N10:78
METER OUT 1 ZERO ADJ P.402 Tunable
Table 7.1 – File N10:x (Drive Read/Write Parameters) for FlexPak 3000 Drives (Continued)
File
Address Parameter Name
Parameter
Number Type Scale