ControNet Network Communication Option Board For Use With FlexPak 3000 and WebPak 3000 DC Drives
3.6 Setting NETW OUT REG 2 SELECT (P.903)
NETW OUT REG 2 SELECT (P.903) defines a parameter number whose value will be
monitored and saved in the network option board’s dual-port memory. For example,
setting this parameter equal to 588 will cause the value of
FIELD DELTA (P.588) to be
written to file address N10:48 in the dual-port memory for FlexPak 3000 drives,
address N10:88 for WebPak 3000 drives.
Range: -32768 to 32767
Type: Non-volatile, Tunable
Default: 0
3.7 Setting NETW OUT REG 3 SELECT (P.904)
NETW OUT REG 3 SELECT (P.904) defines a parameter number whose value will be
monitored and saved in the network option board’s dual-port memory. For example,
setting this parameter equal to 588 will cause the value of
FIELD DELTA (P.588) to be
written to file address N10:49 in the dual-port memory for FlexPak 3000 drives,
address N10:89 for WebPak 3000 drives.
Range: -32768 to 32767
Type: Non-volatile, Tunable
Default: 0
3.8 NETW COMM STATUS (P.908)
NETW COMM STATUS (P.908) indicates the status of network communication.
When
NETW COMM STATUS = NOT ACTIVE, the network option board is not
communicating on the ControlNet network.
When
NETW COMM STATUS = ACTIVE, the network option board is communicating
properly with the ControlNet network.
Range:
NOT ACTIVE (1), ACTIVE (2)
Type: Read-only (output)
3.9 NETW TYPE & VERSION (P.909)
NETW TYPE & VERSION indicates the type of network board installed and its software
version. The format is of the form TV.VV, where:
T = board type:
2 = AutoMax, Profibus, InterBus
4 = DeviceNet (FlexPak 3000 drives only)
5 = ControlNet
V.VV = major and minor version numbers (e.g. 1.03)
Range: 10.00 to 99.99
Type: Read-only (output)