Energy Saving Package Instruction Manual

A-2 Specifications and City Climate Profiles
Allen-Bradley® FanMaster™ Energy Saving Package Installation Manual - Publication FANM-IN001B-EN-P – December, 2009 PN-65329
Inputs and Outputs Inputs:
Supply Air Temp. @ 4…20 mA = 0°…100°C (32°…212°F)
Mixed Air Temp. @ 4…20 mA = 0°…100°C (32°…212°F)
CO
2
@ 4…20 mA = 0…2000 ppm
Damper Position Switch (when not using constant vent. option) = DC
contact closed when open > minimum (Economizer active)
BAS Start (full only) = 115V AC or 24V AC signal
Current Switch (evaluation unit only) = DC contact closed when fan
running
Supply Fan Drive Running = Contact on drive closed when supply fan
drive running
Supply Fan Drive Status and Speed Feedback (via Modbus RTU)
Return Fan Drive Status and Speed Feedback (via Modbus RTU, when
installed)
Outside Air Damper Command from BAS (required only w/constant vent.
option) @ 4…20 mA = 0…100% open command
Pressure (optional w/pressure override) @ 4…20 mA = -0.100…0.100
InWC building pressure to outside pressure difference
Outputs:
High CO2 Alarm = Isolated contact closed
Supply Fan Proof of Flow = Isolated contact closed
FanMaster Not Faulted = Isolated contact closed
Damper Override (force outside air damper closed) - (used only when not
using constant vent. option) = Isolated contact closed
Damper Command to Outside Air Damper - connect at supply fan drive
analog output 1 terminals (required only w/constant vent.) @ 4…20 mA =
0…100% open command
Supply Fan Start/Stop and Speed Reference (via Modbus RTU)
Return Fan Start/Stop and Speed Reference (via Modbus RTU, when
installed)
Instrumentation Temperature Transmitter (2): 0°…100° C (32°F
212°F) Duct Insertion
CO
2
Sensor: 02000 ppm, Duct Mount
Damper Switch:
Type: Mechanical
Rating: 5 A, 120/250V AC
Operation: SPDT
Angle: N.O. makes 20 degrees above horizontal, breaks 15 degrees
below horizontal
Operating Temp.: -30°…130°F (-34°…54°C)
Enclosure: UL 94V-0 flammability rating
Optional
Instrumentation
Current Switch (provided w/evaluation unit only):
Type: AC/DC
Switch Voltage Max.: 30V AC/40V DC
Current Max.: 500 mA
Voltage on @ 24V DC , 150 mA: < 0.1V
Input Current Min.: 1.5 A
Input Current Max.: 200 A
Recommended Modus T30 or M30 Differential Pressure Transmitter
(customer supplied):
Supply Voltage: 11…32V DC
Power: 0.9 VA
Analog Output: 4…20 mA limited to approx. 3.85 mA at low end of span,
approx. 25 mA at upper end
Overpressure: 8 x pressure range or 8'' W.C. (1992.8 Pa), whichever is
greater
Operating Temp.: 0°…45°C (32°…115°F)
Medium: Air or inert gases
Category Specification