Energy Saving Package Instruction Manual

C-18 FanMaster Screens and Field Descriptions
Allen-Bradley® FanMaster™ Energy Saving Package Installation Manual - Publication FANM-IN001B-EN-P – December, 2009 PN-65329
System Status Screen
The System Status screen is used to display additional detailed monthly
energy and savings data collected by the FanMaster.
Table C.Q System Status Screen Fields
Field Name Description
Spd Command % Current percentage of supply fan motor full speed.
(Normal Speed) Indicates that the supply fan motor is at “Minimum”, “Normal” or “Full”
speed.
Supply Air Temp (°F) Current supply air temperature.
Mixed Air Temp (°F) Current mixed air temperature.
Delta-T (°F) Current difference in air temperature between the mixed and supply air.
CO2 Level (ppm) Current CO
2
level (if monitored).
Avg CO2 Level (ppm) Current average monthly CO
2
level (if monitored).
Bldg Pres (InWc) Current building air pressure (if monitored).
BAS Damper Cmd % Current outside air damper percentage open as commanded by the BAS.
BAS Start / Stop Signal Indicates whether the BAS is currently commanding the supply air fan to
“Start” or “Stop”.
Damper Position Indicates whether the outside air damper is currently in the “Min”, “Max” or
“Econ” position.
Htg/Clg Mode Indicates whether the AHU is currently in “Cooling”, “Heating” or “Sat”
mode.
Data Collect Indicates whether data collection is currently “Collecting” or “Stopped”.
(02/24/2009 09:34) Current date and time.
Dashboard Press to view the Dashboard Screen
.
AHU Press to view the Air Handler Unit Diagram Screen
.
System Status Screen you are currently viewing.
Data Log Press to view the Data Log #1 Screen
.
Set Date Press to view the Setup Date and Time Screen
.
Setup press to view the Setup Screen #1
.