Item Description
PIOrFTLDTimestamp The PIOrFTLDTimestamp key specifies which time stamp
will be used to determine when to send data to the
FactoryTalk Historian server. PIOrFTLDTimestamp=0 means
the FactoryTalk Historian server time stamp is used, and 1
means the FTLD server time stamp is used. This setting is
similar to the /TSofPIorFT command-line parameter. See
"Command-line Parameters (page 39)" for more
information.
FTLDResponseInterval The FTLDResponseInterval key specifies the time interval
during which the FTLD interface checks for data points that
were marked ‘bad_quality’ by the FTLD service. The FTLD
service will mark a data point ‘bad_quality’ if the data point
links to an incorrect item (data point) in the FactoryTalk
Diagnostics, or if the FTLD service was not able to receive a
data point from the FTLD interface because several other
data points were being added to the FactoryTalk Historian
server at that time. The period can be set in milliseconds
(ms). The default is 5000 ms.