Chapter 5 Point Configuration
24 Rockwell Automation Publication HSELD-UM024A-EN-E–September 2013
The Point Source is a unique single or multiple character string that
is used to identify the PI point as a point that belongs to a particular
interface. The Point Source for FactoryTalk Historian Live Data
Interface is FTLD. For additional information, see the /ps
command-line parameter description in "Command-line Parameters
(page 39)".
Typically, device point types do not need to correspond to Historian
point types. For example, integer values from a device can be sent to
floating-point or digital Historian tags. Similarly, a floating-point
value from the device can be sent to integer or digital Historian tags,
although the values will be truncated.
The following point types are supported on PI 3 Servers:
float16
float32
float 64
int16
int32
digital
string
NOTE
For more information on the individual point types, refer to the
FT Historian SE Server Reference Guide, available in the Common
Files > Rockwell > Help folder in your Program Files
directory.
Location1 indicates to which copy of the interface the point belongs.
The value of this attribute must match the /id startup parameter.
The default value for the FTLD Local Interface is 1.
Point Source
Point Type
PI 3 Server Nodes
Location1