t Owner manual

70 Rockwell Automation Publication IASIMP-QS016C-EN-P - October 2014
Chapter 3 Energy Data Collector Configuration
The Ethernet communication parameters are listed in this table.
4. To change a parameter:
a. Press Enter to select a menu item.
b. Press the Up and Down arrows to change the value.
c. When the desired value is displayed, press Enter to confirm your selection.
5. Press Esc to return to the main menu.
Configure Basic Device Parameters
1. From the main programming menu, use the Up and Down Arrows to scroll through the programming menu and
view the configuration for the basic device parameters.
2. To change a parameter:
a. Press Enter to select a menu item.
b. Press the Up and Down arrows to change the value.
c. When the desired value is displayed, press Enter to confirm your selection.
3. Press Esc to return to the main menu.
Configure Advanced Parameters
Follow these steps to configure the advanced parameters for the PowerMonitor 500 device. These settings include the
demand calculation mode, interval time, and synchronization mode.
1. From the main programming menu, use the Up and Down Arrows to scroll through the programming menu.
2. Select a menu item by pressing Enter.
Parameter Range Default
IP Address www.xxx.yyy.zzz N/A
Subnet www.xxx.yyy.zzz N/A
Gateway www.xxx.yyy.zzz N/A
TCP IP Port 1…9999 502
ACD Yes or No No
Parameter Range Default
System 1P, 2P, 3P, 3P.n,3P.1, 3P.2 3P.n
CT Ratio 1.0…9999 1.0
PT Ratio 1.0…9999 1.0