t Owner manual
Rockwell Automation Publication IASIMP-QS016C-EN-P - October 2014 65
Energy Data Collector Configuration Chapter 3
Configure Advanced Device Parameters
Follow these steps to configure advanced demand parameters for the PowerMonitor 1000 device. These settings include
demand source, demand period length, and the number of demand periods to average for the demand calculation. The
Advanced Device Configuration Parameters
table on page 65 shows the demand parameters and example settings.
1. Choose Configure
Options>Advanced to
access the Advanced
Configuration page.
2. Enter the default password
of 0 or another valid password to access Edit mode.
3. Set appropriate values for the demand parameters
(elements 14, 15, and 16).
For this example, accept the default parameters as shown.
4. Click Submit to send the parameter changes to the PowerMonitor 1000 device.
TIP
The password appears as asterisks (*).
If you don’t know the password, call
Rockwell Automation technical
support for assistance.
Advanced Device Configuration Parameters
Parameter Range Default Example Settings
Password 0…9999 0 0
Demand Source 0…3
0 = Internal Timer
1 = Status Input 2
2 = Controller Command
3 = Ethernet Demand Broadcast
00
Demand Period Length 0…99 min 15 min 15
Number of Demand Periods 1…15 1 1
Forced Demand Sync Delay 0… 90 s 10
Demand Broadcast Master Select 0…1 0
Broadcast Port Number
(Ethernet Setup)
300… 400 300