t Owner manual

64 Rockwell Automation Publication IASIMP-QS016C-EN-P - October 2014
Chapter 3 Energy Data Collector Configuration
2. Enter the default password of 0 or another valid
password to access Edit mode.
3. Enter the value of the Voltage Mode you are using.
4. Set elements 2, 3, and 4 to configure the PT and
CT parameters.
5. Click Submit to send the parameter changes to the
PowerMonitor 1000 device.
TIP
The password appears as asterisks
(*)
.
If you don’t know the password,
call Rockwell Automation technical
support for assistance.
Analog Input Setup Parameters
Parameter Range Default Example Settings
Password 0…9999 0 0
Voltage Mode 0…6
0 = Direct Delta
1 = Open Delta
2 = Wye
3 = Single Phase
4 = Demo, simulated results
5 = 1PT1CT-LL
6 = 1PT1CT-LN
22
PT Primary 1.0… 50,000 480 480
PT Secondary 5.00… 50,000 480 480
CT Primary 5.00… 50,000 5 600
System PF Setting 0 = Lead (-97…89)
1 = High (-85…98)
2 = Low (-52…-95)
2 = Low 2