t Owner manual

Rockwell Automation Publication IASIMP-QS016C-EN-P - October 2014 61
Energy Data Collector Configuration Chapter 3
Advanced Device Configuration Parameters
Parameter Range Default Example Settings
New Password -1
9999 0000 0000
Demand Period Length -99
99 min 15 15
Number of Demand Periods 1
15 1 1
Forced Demand Delay 0
900 s 10 10
Predicted Demand Type Instantaneous
1st Order
2nd Order
Instantaneous
KYZ Control Source 0 = None
1 = Wh Forward
2 = Wh Reverse
3 = VARh Forward
4 = VARh Reverse
5 = Vah
6 = Ah
7 = Setpoint
8 = Comms
7 = Setpoint
KYZ Pulse Output Scale 1
30000 10
KYZ Pulse Output Width 0, 40
2000 0
Relay Control Source Same as KYZ 7 = Setpoint
Relay Pulse Output Scale 1
30000 10
Relay Pulse Output Width 0, 40
2000 100
RMS Resolution Nominal / High High
(2)
(2) Factory default for RMS Resolution is Nominal for the M4 and High for the M5, M6, and M8.
RMS Averaging On / Off On
Frequency Averaging On / Off On
Date Format MM/DD/YYYY DD/MM/YYYY MM/DD/YYYY
Date: Year 1998
2097 1998
Date: Month 1
12 1
Date: Day 1
31 1
Time: Hour 0
23 0
Time: Minutes 0
59 0
Time: Seconds 0
59 0
Default relay state on comms loss 0 = Last state/resume
1 = Last state/freeze
2 = De-energize/resume
3 = De-energize/freeze
0
Default KYZ state on comms loss 0
Wdog action 0 = Halt
1 = Continue
0 = Halt
Display Module Scroll Speed Fast / Slow Fast
Energy counter rollover point 4
15 digits 15
Metering Result Set (M8 only
(1)
)
(1) Metering result set parameter may only be configured by using communication.
0 = All results
1 = Transducer mode
2 = Energy meter mode
0 = All results