t Owner manual
430 Rockwell Automation Publication IASIMP-QS016C-EN-P - October 2014
Appendix B Custom Units and Value Types
2. Enter a name for the value type.
In this example, enter Fuel Oil Usage. This value type is used
for the Fuel Oil Meter.
3. Choose a Unit.
For this example, select Gal.
4. Check Consumption and/or Demand.
For this example, only Consumption will be logged for the
Fuel Oil, Propane, Water, Natural Gas, Steam, and Air meters.
Demand is typically associated only with electric meters.
5. Click Save.
6. Repeat steps 1…4 to add value types for:
• Propane Usage
• Wat e r Us a g e
• Natural Gas Usage
• Steam Usage
• Air Usage
Enter the settings from the table for each
value type.
When done, the new value types should appear in
the list.
Value Type Name Unit Consumption Demand
Propane Usage Gal Check Uncheck
Water Usage Gal Check Uncheck
Natural Gas Usage thm Check Uncheck
Steam Usage lbs Check Uncheck
Air Usage cf Check Uncheck