t Owner manual
38 Rockwell Automation Publication IASIMP-QS016C-EN-P - October 2014
Chapter 2 System Configuration and Wiring
For the Efficient Industries Plant 1 example, the electricity energy data point listing would look like this.
4. Identify other digital energy data points in close proximity that you can connect to the status inputs of the
PowerMonitors.
For the Efficient Industries Plant 1 example, the air flow digital pulse meter is near the Production 2 electrical
substation so it can connect to the PowerMonitor 1000 named Production 2.
5. Select a Device Class and Meter Type on the FactoryTalk EnergyMetrix tab of the Energy Data Worksheet for the
PowerMonitor status inputs identified in step 4.
a. Select the appropriate PowerMonitor Device Class.
b. Select PM Status Input for the Meter Type.
For the Efficient Industries Plant 1 example, the entries for the air flow data point would look like this.