t Owner manual

Rockwell Automation Publication IASIMP-QS016C-EN-P - October 2014 377
Demand Control Chapter 12
Demand Control Configuration
Prior to configuring the loads in the controller, you must assign priority levels and interlock times to the loads in your
application. The configuration for the Efficient Industries Plant 1 Example is shown below:
Priority Levels
There are up to 16 priority levels available.
Loads with the largest priority number are shed first (priority level 1 is shed last).
More than one load may be assigned to a given priority level. If loads share the same priority level, they will be shed
based on the time since the load was last shed. (In other words, when a shed is required, the running load with the
largest priority level number and the longest minutes since shed will be the next load to shed.)
Interlocks
On Delay interlock is the minimum time the load must be off, in seconds, before it can be restarted.
Off Delay interlock is the minimum time the load must be on, in seconds, before it can be shed.
Max Off Time interlock is the maximum amount of time, in seconds, that the load is allowed to be shed per hour.
Configure the individual loads and the demand control schedule.
1. Click the configuration button on the toolbar.
Load Description Rated KW Priority On Delay (s) Off Delay (s) Max Off Time (s)
1 Air Compressor 1 21 1 60 60 900
2 Air Compressor 2 21 1 60 60 900
3 AHU 1 Production 15 4 120 120 1800
4 AHU 2 Production 15 4 120 120 1800
5 AHU 3 Shipping 12 5 120 120 1800
6 AHU 4 Office 10 7 120 120 1800
7 Exhaust Fan 1 2 2 30 30 2700
8 Exhaust Fan 2 2 2 30 30 2700
9 Exhaust Fan 3 2 10 30 30 2700
10 Exhaust Fan 4 2 10 30 30 2700
11 Lighting Production 6 3 15 15 1200
12 Lighting Production 6 6 15 15 1200
13 Lighting Shipping 6 8 15 15 3600
14 Lighting Office 6 9 15 15 3600