t Owner manual
Rockwell Automation Publication IASIMP-QS016C-EN-P - October 2014 367
Demand Control Chapter 12
8. Click Enter.
9. Use the same procedure to configure the I/O mapping for the remaining loads in rungs 3…32.
If you are not utilizing all 16 loads in your application, you can delete the unused I/O mapping rungs, or leave them as is.
Configure PowerMonitor Messages
Follow these steps to configure PowerMonitor unit messages.
1. If you are using a PowerMonitor 1000, skip to step 2.
If you are using a PowerMonitor 5000, you must edit the main routine.
a. Expand the DemandControl program and double-click the MainRoutine.
b. In rung 5, modify the JSR instruction to call the SR01_ProcessPM5000 routine.
2. Expand the DemandControl program and double-click the SR01_ProcessPM1000 or SR01_ProcessPM5000
routine as required per your application.
Rung 1 includes several message instructions.
3. For each message, click the View Configuration
Dialog button to launch the configuration window.
IMPORTANT
The demand control program is configured to use a PowerMonitor 1000 by default.