t Owner manual
Rockwell Automation Publication IASIMP-QS016C-EN-P - October 2014 329
FactoryTalk View ME Energy Faceplates Chapter 11
17. Repeat steps 1…16 for each PowerMonitor 1000 or 3000 status input in your system.
Table 5 - Energy Add-On Instruction Factors for Electric Inputs
Energy Factor Tag Description
Set_Demand_Interval The value, in minutes, used to calculate the End of Demand Interval (EOI). This value is used only if the Val_End_of Demand_Type is 2.
Set_Demand_Delay The time value used to reset the end of interval after the Set_Demand_Interval value has been exceeded without a utility contact or master
end of demand contact closure. The value must be between 0…90 seconds.
Set_End_of_Demand_Interval_Type The value that defines how the End of Demand Interval (EOI) is triggered.
1 = A local digital input connected to an electric utility meter EOI contact (Inp_End_of_Demand_Utility_Contact).
2 = An internal PLC timer (Demand_Interval _PLC Timer) that is typically used when an electric utility meter EOI contact is not available.
3 = A master command input (CMD_Master_End_Of_Demand_Interval) typically from a central controller that is used to synchronize
multiple electric meter EOIs.
Set_High_Demand When the demand (kW) value exceeds the Set_High_Demand, the High Demand Fault is set.
Set_Critical_Demand When the demand (kW) value exceeds the Set_Critical_Demand, the High Critical Fault is set.
Table 6 - Energy Add-On Instruction Factors for Gas, Propane, Fuel Oil, Steam, Air and Water Inputs
Energy Factor Tag Definitions
Set_Calc_Interval The time interval, in minutes, used to calculate the average energy flow.
For example, an interval value of 5 will calculate the average energy flow every 5 minutes.
Set_High_Flow When the flow rate value exceeds the Set_High_Flow value, the High Flow Fault is set.
Example
: A value of 1000 will set the High Flow Fault in the Energy_Gas_PM_Status Add-On Instruction when the gas flow rate
exceeds 1000 therms/hr.
Set_Critical_Flow When the flow rate value exceeds the Set_Critical_Flow value, the Critical Flow Fault is set.
Example
: A value of 1500 will set the Critical Flow Fault in the Energy_Gas_PM_Status Add-On Instruction when the gas flow rate
exceeds 1500 therms/hr.
TIP
The meter pulse factor, consumption value of each input pulse, is set within the PowerMonitor configuration. Refer to Configure
CompactLogix Energy Inputs, on page 80.
TIP
For additional information on how these energy factors affect calculations, refer to Appendix C, Energy Electric Add-On
Instructions and Appendix D, Digital and Analog Energy Add-On Instructions
Energy Add-On InstructionDefault Flow Rate Unit
Air cfm (cubic feet per minute)
Fuel Oil, Propane, Water gpm (gallons per minute)
Gas therms/hr
Steam lbs/hr
Energy Add-On InstructionDefault Flow Rate Unit
Air cfm (cubic feet per minute)
Fuel Oil, Propane, Water gpm (gallons per minute)
Gas therms/hr
Steam lbs/hr