Rockwell Automation Publication IASIMP-QS016C-EN-P - October 2014 317
FactoryTalk View ME Energy Faceplates Chapter 11
Configure Device Logic for Equipment Status and Alarm History Faceplates
Some logic is required in the CompactLogix controller for PowerMonitor 1000 and 3000 devices to support the
Equipment Status and Alarm History Faceplates.
Configure PowerMonitor 1000 and 3000 Communication
Follow these steps to add the PowerMonitor 1000 and 3000 devices to your Ethernet network in the CompactLogix I/O
Configuration.
1. Browse to the CompactLogix Ethernet network in
the I/O Configuration.
2. Right-click Ethernet and choose New Module.
3. Choose Communication.
4. Scroll through the modules and choose the
ETHERNET-MODULE (Generic Ethernet
Module).
5. Click OK.
TIP
The faceplate logic required for the CompactLogix energy inputs is included in the Energy Add-On Instructions that were
configured in Configure CompactLogix Energy Inputs
on page 86.
TIP
The equipment status faceplate logic required for the PowerMonitor 500, PowerMonitor 5000, PowerFlex Drives, E3 Plus, E300,
SMC-50, and CIP Motion Drives is included in the faceplate routines that were configured in the previous sections.