FactoryTalk EnergyMetrix Software and PowerMonitor Device Maintenance Chapter 10
12. Edit the Maintenance Cleanup Task.
a. Select the backup folder used for the backups as the
search target, and enter the BAK file extension.
b. Select to delete files older than 1 week.
13. Click the browse icon next to the
Schedule field.
14. Set up a recurring schedule to occur daily
at a convenient time, then Click OK.
15. Click the Save icon to save the
maintenance plan.
If notified that the SQL Agent is not
running, follow the prompts to autostart the SQL Agent.
16. When done, close SQL Management Studio.