Manual

Using Multi-Drive Mode
8-7
Module Settings for the Example Program
The Mode Jumper on the module is set to the Multi-Drive
operation position. See section 3.2, Commissioning the Module.
All DIP switches on the module are set to CLOSED (all 0s). See
section 3.2, Commissioning the Module. The actual node address
will be set via a software parameter.
The following module parameters are set:
Important: Drive node addresses change only after a power cycle.
Drive Settings for the Program Example
Parameter Value Description
02 - (DN Addr Cfg) 1 DeviceNet node address
15 - (DSI I/O Cfg) 4 “Drives 0-4” — 5 drives on 1 node
17 - (Drv 0 Addr)
1
1 Modbus address of Drive 0
18 - (Drv 1 Addr) 2 Modbus address of Drive 1
19 - Drv 2 Addr) 3 Modbus address of Drive 2
20 - (Drv 3 Addr) 4 Modbus address of Drive 3
21 - (Drv 4 Addr) 5 Modbus address of Drive 4
1
The settings for these parameters must match the parameter A104 (Comm
Node Addr) settings in the respective drives.
Parameter
Value
Drive 0 Drive 1 Drive 2 Drive 3 Drive 4
P36 - (Start Source) 5 5 5 5 5
P38 - (Speed Reference) 5 5 5 5 5
A103 - (Comm Data Rate) 4 4 4 4 4
A104 - (Comm Node Addr)
1
12 345
A105 - (Comm Loss Action) 0 0 0 0 0
A106 - (Comm Loss Time) 5 5 5 5 5
A107 - (Comm Format) 0 0 0 0 0
1
The settings for these parameters must match the respective parameter
settings in the module (parameter 17 (Drive 0 Address) through parameter
21 (Drive 4 Address)).