Manual

B-2
DeviceNet Communications Module
Displays the Single- or Multi-Drive operating mode selected with
jumper on the module.
Sets the node address used by the drive after a reset or power
cycle. This setting is used when all of the module DIP switches are
in the CLOSED position (all 0s).
Displays the DeviceNet node address currently being used by the
module.
Sets the DeviceNet data rate after a reset or power cycle. This
setting is used when all of the module DIP switches are in the
CLOSED position (all 0s).
1 Mode
Range: 0 = Single Drive
1 = Multiple Drive
Default: 0 = Single Drive
Type: Read Only
Reset Required: N/A
2 DN Addr Cfg
Range: 0 to 63
Default: 63
Type: Read/Write
Reset Required: Yes
3 DN Addr Act
Range: 0 to 63
Default: 63
Type: Read Only
Reset Required: N/A
4 DN Rate Cfg
Range: 0 = 125 kbps
1 = 250 kbps
2 = 500 kbps
3 = Autobaud
Default: 3 = Autobaud
Type: Read/Write
Reset Required: Yes