Troubleshooting 8-3
MOD Status Indicator
Status Cause Corrective Action
Off The adapter is not powered. Securely connect the adapter to the drive
using the ribbon cable.
Apply power to the drive.
Flashing
Red
The adapter has failed the
firmware test, connected drive
is faulted, or a drive is missing
in Multi-Drive mode.
Clear faults in the drive.
Cycle power to the drive.
If cycling power does not correct the
problem, the parameter settings may have
been corrupted. Reset defaults and
reconfigure the module.
If resetting defaults does not correct the
problem, flash the adapter with the latest
firmware release.
For Multi-Drive mode, determine which
drive is missing or faulted. Check cabling
and configuration settings (see Configuring
the RS-485 Network section in Chapter 7).
Solid
Red
The adapter has failed the
hardware test.
Cycle power to the drive.
Replace the adapter.
Flashing
Green
The adapter is operational,
but is not transferring I/O data.
Place the scanner in RUN mode.
Program the controller to recognize and
transmit I/O to the adapter.
Configure the adapter for the program in
the controller.
Normal behavior if no DSI I/O is enabled.
Solid
Green
The adapter is operational
and transferring I/O data.
No Action.