User manual

Using Multi-Drive Mode 7-7
Drive Settings for the Example Program
The following common Tags are used:
The following Tags are used for Drive 0:
Parameter
Value
Drive 0 Drive 1 Drive 2 Drive 3 Drive 4
P36 - [Start Source] 5 5 5 5 5
P38 - [Speed Reference] 5 5 5 5 5
A103 - [Comm Data Rate] 4 4 4 4 4
A104 - [Comm Node Addr]
(1)
(1)
The settings for these parameters must match the respective parameter
settings in the adapter (Parameter 17 - [Drive 0 Address] through
Parameter 21 - [Drive 4 Address]).
1 2 3 4 5
A105 - [Comm Loss Action] 0 0 0 0 0
A106 - [Comm Loss Time] 5 5 5 5 5
A107 - [Comm Format] 0 0 0 0 0
ControlLogix Example
Tag Name Type Description
Local : 3 : I AB: 1756_D...
1756-DNB I/OLocal : 3 : O AB: 1756_D...
Local : 3 : 5 AB: 1756_D...
Drive Input Image INT [10] Input Image Table
Drive Output Image INT [10] Output Image Table
Tag Name Type Description
Drive 0 Command Stop BOOL Logic Command bit 0 (STOP)
Drive 0 Command Start BOOL Logic Command bit 1 (START)
Drive 0 Command Jog BOOL Logic Command bit 2 (JOG)
Drive 0 Command Clear Faults BOOL Logic Command bit 3 (CLEAR FAULTS)
Drive 0 Command Forward BOOL Logic Command bit 4 (FORWARD)
Drive 0 Reference INT Speed Reference
Drive 0 Status Ready BOOL Logic Status bit 0 (READY)
Drive 0 Status Active BOOL Logic Status bit 1 (ACTIVE)
Drive 0 Status Forward BOOL Logic Status bit 3 (FORWARD)
Drive 0 Status Faulted BOOL Logic Status bit 7 (FAULT)
Drive 0 Status At Reference BOOL Logic Status bit 8 (AT SPEED)
Drive 0 Feedback INT Speed Feedback
Perform Parameter Read 0 BOOL Initiates the parameter read
Parameter RD Value 0 INT Read value of the parameter
Parameter RD Message 0 MESSAGE Get_Attribute_Single (Read)