7-6 Using Multi-Drive Mode
The example ladder logic program demonstrates using Multi-Drive
mode with five drives. See Figure 7.2
for a system layout diagram.
Function of the Example Program
The example program provided is for the ControlLogix, but other
controllers can also be used. The following actions can be performed:
View status information from the drives such as Ready, Fault, At
Speed, and Feedback.
Control the drives using various Logic Command bits (Stop, Start,
etc.) and Reference.
Perform a single parameter read and write for each drive. The
example uses drive Parameter 39 - [Accel Time] for both so you
can see (read) the change after a write is performed.
Adapter Settings for the Example Program
The Mode Jumper on the adapter is set to the Multi-Drive operation
position. See Chapter 2, Commissioning the Adapter.
All DIP switches on the adapter are set to CLOSED (all 0’s). See
Chapter 2, Commissioning the Adapter. The actual node address will
be set via a software parameter.
The following adapter parameters are set:
Multi-Drive Ladder Logic Program Example
Parameter Value Description
02 - [DN Addr Cfg] 1 DeviceNet node address
15 - [DSI I/O Cfg] 4 “Drives 0-4” — 5 drives on 1 node
17 - [Drv 0 Addr]
(1)
(1)
The settings for these parameters must match the Parameter A104 -
[Comm Node Addr] settings in the respective drives.
1 Modbus address of Drive 0
18 - [Drv 1 Addr] 2 Modbus address of Drive 1
19 - [Drv 2 Addr] 3 Modbus address of Drive 2
20 - [Drv 3 Addr] 4 Modbus address of Drive 3
21 - [Drv 4 Addr] 5 Modbus address of Drive 4