|Data size larger than 255 bytes |Configure the device for a
85 | |smaller data size. OR the
|OR a run time data size error received. |slave has a variable
| |connection size which AB
| |scanners do not support.
---------------|-----------------------------------------|------------------------------|
|Device is producing zero length data |Check device configuration
86 |(idle state) while channel is in |and slave node status.
|Run Mode. |
---------------|-----------------------------------------|------------------------------|
88 |Shared inputs error also appears at |Check connection of master to
|power-up and reset, the module displays |slave that is configured for
|all 14 segments of the node address and |shared inputs - it may be
|status display LEDs. |powered down or disconnected.
---------------|-----------------------------------------|------------------------------|
89 |This is an ADR error. The Device does |Check configuration or disable
|not support the Auto-Device Recovery |the ADR function for this
|or is not configured properly. |device.
---------------|-----------------------------------------|------------------------------|
|User has disabled communication port |Reconfigure your module.
90 | |Check Module Command Register.
| |
---------------|-----------------------------------------|------------------------------|
|Bus-off condition detected on comm port. |Check DeviceNet connections and
91 |Scanner is detecting communication errors|physical media integrity.Check
| |system for failed slave devices
| |or other possible sources of
| |network interference.
---------------|-----------------------------------------|------------------------------|
|No network power detected on comm port. |Provide network power.
92 | |Make sure that scanner drop
| |cable is providing network
| |power to scanner comm port.
---------------|-----------------------------------------|------------------------------|
|Application FLASH update in progress. |None. Do not disconnect the
95 | |module while application FLASH
| |is in progress. You will lose
| |any existing data in the
| |scanner's memory.
---------------|-----------------------------------------|------------------------------|
|Scanner halted by user command. |Check ladder program for cause
97 | |of fault bits.
| |
---------------|-----------------------------------------|------------------------------|
|Unrecoverable firmware failure. |Service or replace your module
98 | |
| |
---------------|-----------------------------------------|------------------------------|
|Unrecoverable hardware failure. |Service or replace your module.
99 | |
| |
----------------------------------------------------------------------------------------|