Installation
Input isolation transformers might be needed to help eliminate the
following:
· Damaging line voltage transients from reaching the drive.
· Line noise from the drive back to the incoming power source.
· Damaging currents that could develop if a point inside the drive
becomes grounded.
Observe the following guidelines when installing an isolation transformer:
· A power disconnecting device must be installed between the power line
and primary of the transformer.
· If the power disconnecting device is a circuit breaker, the circuit breaker
trip rating must be coordinated with the in-rush current (10-12 times full
load current) of the transformer.
Optional isolation transformer
ATTENTION: Distribution system capacity above the maximum
recommended system KVA requires the use of an isolation transformer,
a line reactor, or other means of adding similar impedance to the drive
power input. Failure to observe these precautions could result in
damage to, or destruction of, the equipment.