User Manual

MCS-E3 Cat. No. Prospective S.C.
current, Ir (A)
Conditional S.C.
current, Iq (A)
Max. voltage (V)
CEP7-C_-23-X
1,000
CEP7-C_-43-X
3,000
CEP7-C_-85-X
5,000
CEP7-C_-180-X
10
,
000
CEP7-C_-420-X
18
,
000
CEP7-C_-860-X
30
,
000
CEP7-C_-CT-5000
1
,
000
100,000 690
Fuse Coordination
Contactor Cat. No.Max. starter FLC
(A)
Prospective S.C.
current, Ir (A)
Conditional S.C.
current, Iq (A)
Max. voltage
(V)
Type I with
Class J fuse (A
)
Type II with
Class J fuse (A)
-23-X
CA7-09 9 20 15
-23-X
CA7-12 12 20 20
-23-X
CA7-16 16 30 30
-23-X
CA7-23 23 40 40
-43-X
CA7-30 30 50 50
-43-X
CA7-37 37 50 50
-43-X
CA7-43 43 70 70
-85-X
CA7-60 60 80 80
-85-X
CA7-72 72 100 100
-85-X
CA7-85 85
5,000
150 150
-180-140, CT-5000 CA6-95 95 200 200
-180-140, CT-5000 CA6-110 110 200 200
-180-140, CT-5000 CA6-140 140 250 250
-180-210, CT-5000 CA6-180 180 300 300
-420-210, CT-5000 CA6-210 210 400 400
-420-210, CT-5000 CA6-250 250 400 400
-420-210, CT-5000 CA6-300 30
0 500 500
-420-302, CT-5000 CA6-210 210 400 400
-420-302, CT-5000 CA6-250 250 400 400
-420-302, CT-5000 CA6-300 300 500 500
-420-420, CT-5000 CA6-300 300 500 500
-420-420, CT-5000 CA6-420 420 600 600
1,000
100,000 600
MCS-E3 Cat. No.
3,000
10,000
CEP7-C1
CEP7-C2
CEP7-C3
CEP7-C5
Table 4 IEC Type 1 and Type II Fuse Coordination with CA6 and CA7 contactors per EN60947-4-1
Table 3 IEC Short Circuit Ratings per EN60947-4-1
PN-17758
DIR 10000010792 (Version 03)
Printed in U.S.A.