Specifications
DeviceNet RS-232 Interface Module 17
Publication
17705.6 - June 1996
Connecting Cables via DeviceNet
Follow
these steps to connect the 1770-KFD module to a DeviceNet network:
1. Connect the DeviceNet cable (trunkline or dropline) to the unsealed
DeviceNet terminal connector.
DeviceNet cable
(trunkline or dropline)
unsealed DeviceNet
terminal connector
20295c
red
white
shield
blue
black
2. Connect the terminal connector to the 1770-KFD module.
Important:
DeviceNet cable connections should match color bars/electrical
diagram on top of 1770-KFD module. See the table below.
pin number wire color abbreviation description
1 black V- power return
2 blue data low data line
3 clear shield between cable jacket and wire
4 white data high data line
5 red V+ positive voltage (hot)