Installation Instructions User guide

The Strain Gauge Converter can request the following information via the RS 485 interface e. g.
from a PC
or a PLC (with 3 decimal places each):
Net measured value (in the set unit)
Gross measured value (in the set unit)
mV measured value (in the set unit)
Output value current output (in mA)
The following commands are available for the requests:
Null: delete the receive buffer of the requesting device
Check_1: checks whether Strain Gauge Converter (with the respective address) is connected
Get_value_ch1: requests the net measured value
Get_value_ch2: requests the gross measured value
Get_value_ch3: requests the mV measured value
Get_current: requests the output value current output
Requests via the RS 485 interface are not suitable for time-critical or safety-critical
applications.
At the beginning of each RS 485 communication, send the re
quest Check_1.
The RS 485 interface is deactivated if a connector is plugged into the programming
jack (RS 232 interface).
When the connector is removed, the request Check_1 is
required to switch to RS 485
communication.
Warning
Note
Bul. 937C Strain Gauge Converter Installation Instructions
39