Installation Instructions User guide

Bul. 937C Strain Gauge Converter Installation Instructions
Gross/Net, Span, Inverted
By means of the Gross/Net parameter, you determine whether the value for the Span is a gross
value or a net value (gross value minus current tare).
By means of the Span parameter, you determine the measured value range which is represented
by the current output.
The span must be entered in the selected unit.
If you h
ave selected Gross, you can enter values between 1 % and 100 % of the maximum cell
load.
If you have selected Net, you can enter values between 1 % of the maximum cell load and the
value of the maximum cell load minus the current tare.
If you select Inve
rted normal, the measured value 0 is converted into the start value of the
current output and the Span is converted into the end value (for the Strain Gauge Converter
always +20 mA). If you select Inverted inverted, the Span is converted into the start value of
the current output and the measured value 0 is converted into the end value.
Fault current
—— Min
Max
Hold
Up/down
Inverted
—— Normal
Inverted
31