Installation Instructions Manual
Bul. 937C HART Loop Converter Installation Instructions
Editing device data: Input
Defining a Characteristic
The choice of characteristic defines th
e limits for measuring underrange and overrange.
Measuring underranges or overranges outside the specified range cannot be analyzed.
If measuring ranges are undercut or exceeded, the minimum or maximum value is
issued constantly.
1.
Sele
ct the characteristic using the or buttons.
2. Select the characteristic 4 - 20 unlim
ited.
For the characteristic 4 - 20 unlimited, measuring underranges are
analyzed linearly up to 0
mA, and measuring overranges are analyzed linearly
up to approx. 23 mA by the device.
3. Select the characteristic 4 - 20 NE43.
For the characteristic 4 - 20 NE43
, measuring underranges are analyzed linearly
up to 3.8 mA, and measuring overranges are analyzed linearly up to 20.5 mA by the
device.
4. Confirm your entry with OK.
Defining the Start Value
Make sure during configuration that the start value is at l
east 1% less than the end value.
If the start value does not meet this requirement, the start value will not be accepted by
the device.
1. Enter the start value as
a floating point figure. For entering floating point figures, see
"Entering Floating Point Figures" . The defined unit from the Unit
menu is used as the unit.
2. Confirm your entry with OK.
Make sure during configuration that the end value is at least 1 % greater than the start value.
1. Enter the end value
as a floating point figure. For entering floating point figures,
see "Entering Floating Point Figures" . The defined unit from the Unit menu
is used as the unit.
2. Confirm your entry with OK.
Defining the End Value
31