Bul. 937C Universal Temperature Converter Installation Instructions
If a current output is operated as a sink, the voltage across the terminals must be between 5 V and
30 V. An additional resistance is only required if the voltage is above 16.5 V. The resistance must be
between (U - 16.5 V)/0.0215 A and (U - 5 V)/0.0215 A (see diagram).
Example: U = 24 V
(24 V - 16.5 V)/0.0215 A = 350 Ω
(24V - 5V)/0.0215A = 880Ω
R [Ω]
1200
1000
800
600
400
200
0
16 20 25 30
U [V]
Resistance area